During operation, Generators may suffer from electrical faults and abnormal operating conditions on stator and rotor windings. Matching relay protection devices are essential to quickly identify anomalies, send alarm signals or trigger shutdown trips. Proper protection configuration can avoid permanent damage to the generator body, guarantee personal safety and maintain the stability of the power grid. This document sorts out common generator faults, abnormal operation states, corresponding protection schemes and basic functions of each protection.
Generator Fault Types
1. Phase-to-phase short circuit of stator winding and lead-out lines
2. Turn-to-turn short circuit of stator winding
3. Single-phase earth fault of stator winding
4. One-point earth fault / two-point earth fault of rotor winding
5.Loss of excitation (excitation current disappears in excitation circuit)
Abnormal Operation Conditions of Generator
1. Stator overcurrent caused by external short circuit
2. Symmetrical overload of stator winding
3. Stator overvoltage caused by sudden load rejection
4. Rotor surface overload caused by external asymmetrical short circuit or asymmetrical load (single-phase load, open-phase operation, etc.)
Generator Protection List
1. Longitudinal differential protection
2. Stator earth fault protection

3. Stator turn-to-turn short circuit protection
4. External phase-to-phase short circuit backup protection
5. Negative-sequence overcurrent protection
6. Stator overload protection
7. Stator overvoltage protection
8. Rotor one-point & two-point earth protection
9. Loss-of-excitation protection
10. Excitation winding overload protection
11. Reverse power protection
12. Overexcitation protection
13. Out-of-step protection
14. For large-capacity generators: underfrequency protection, overfrequency protection, start-stop protection, accidental energization protection, breaker flashover protection
15. Non-electrical protection: water-cut protection for water-cooled generators
Protection Function Description
1. Longitudinal differential protection: Main protection for phase-to-phase short circuit of stator winding and leads, trips for shutdown.
2. Stator earth fault protection: For stator single-phase earth fault. 100% stator earth protection covers full winding, alarms or trips.
3. Stator turn-to-turn short circuit protection: Detects turn-to-turn and branch short circuit, trips for shutdown.
4. External phase-to-phase short circuit protection: Backup protection for external faults, normally low-voltage blocked overcurrent protection, trips.
5. Negative-sequence overcurrent protection: Responds to negative-sequence current from asymmetrical faults/loads, prevents rotor surface overheating, alarms or trips.
6. Stator overload protection: Detects symmetrical stator overload, alarms and may reduce load.
7. Stator overvoltage protection: Prevents insulation damage from overvoltage after load rejection, trips.
8. Rotor earth protection: One-point earth: alarm; two-point earth: trip and shut down, avoid rotor short circuit and core burn.
9. Loss-of-excitation protection: Monitors loss of excitation, prevents out-of-step and system voltage collapse, reduces power or trips.

10. Excitation winding overload protection: Detects overload of excitation winding, alarms or limits excitation current to avoid overheating.
11. Reverse power protection: Prevents generator motoring mode and prime mover damage (steam turbine blades), trips for shutdown.
12. Overexcitation protection: Protects generator/transformer core against overexcitation, prevents core overheating and insulation aging, alarms or trips.
13. Out-of-step protection: Reduces electromagnetic damage and shaft fatigue during asynchronous operation, trips or enables resynchronization control.
14. Underfrequency / overfrequency protection: Monitors abnormal frequency, avoids mechanical resonance and equipment damage. Accidental energization / start-stop protection: prevents wrong synchronization at non-rated speed and faults during start-stop process.
15. Non-electrical protection (water cut, temperature, vibration): Monitors cooling system and mechanical status, alarms or trips to secure equipment.
All generator protections coordinate together. Main protections quickly clear severe internal faults; backup and auxiliary protections handle abnormal conditions and external faults. Non-electrical protections supplement electrical relays for mechanical and cooling issues. Proper selection, setting and routine testing boost generator safety and reliability for steady power supply.
If you have any electrical related or other technical questions about generator faults, protection configuration, parameter debugging and unit operation, you can contact us-reach me faster via WhatsApp: +8619317493200 and Email: dingbo5@dieselgeneratortech.com. We have a professional and technical team with an average working experience of more than 10 years in the generator industry.