After diesel generator sets have been used for a long time, some faults are unavoidable. Many users encounter a high-temperature diesel generator coolant boiling phenomenon during operation, that is, the cooling system temperature is too high, causing the coolant to boil and steam. Coolant boil-over not only affects the normal operation of the generator set, if handled improperly, it may cause serious damage to the engine. So how should this situation be handled? Below Dingbo Power shows you some common causes of this fault and the correct countermeasures.
Common causes of diesel generator coolant boiling
1. Insufficient coolant. Leakage in the radiator or piping, or failure to replenish coolant for a long time. When the circulating water volume of the diesel engine is insufficient, especially under high load or continuous load operation, the temperature of the lubricating oil will also rise, further causing the water temperature to continue climbing.
2. Radiator blockage. The external fins of the radiator are blocked by willow catkins and dust, scale accumulates on the inner walls of the radiator tubes, resulting in poor heat dissipation of diesel generator set and likewise causing the water temperature to rise and boil.
3. Fan failure. The fan belt slips or breaks. Damage to the cooling fan, whether missing blades or damaged blade edges, will cause insufficient cooling airflow and a rise in water temperature. If the diesel engine cooling fan belt is too loose, the cooling fan cannot reach the expected speed, resulting in insufficient cooling airflow, which will cause the water temperature to continue rising.
4. Thermostat failure. If the diesel generator thermostat cannot open, the coolant always remains in small circulation, which will also cause the water temperature to rise.
5. Water pump failure. The water pump impeller is worn, and the cooling water circulation flow is insufficient. Damage to the diesel engine freshwater circulating pump will also affect water circulation, thereby causing an abnormal rise in water temperature.
6. Cylinder head gasket or cylinder head cracking. If the diesel engine cylinder head gasket is damaged and blown, or if the cylinder head cracks, high-pressure gas in the cylinder will intrude into the water cooling system, thereby causing a boiling phenomenon, often accompanied by emulsification of the diesel engine oil.
7. Air in water pipes. If air exists in the diesel engine water pipes, after startup the outlet pipe may have poor circulation due to an air lock, which will lead to a rise in water temperature and intermittent water spraying, similar to a diesel generator coolant boiling phenomenon.
8. Environmental factors: Ambient temperature too high, poor ventilation in the generator room, and poor intake and exhaust airflow.
Solutions for coolant boiling in diesel generator sets
When this phenomenon occurs, remember not to shut down the engine immediately, so as to avoid burning the cylinder head gasket, scoring the cylinders, and causing greater damage accidents to the diesel generator set. Do not attempt to open the radiator cap; otherwise, scalding liquid may spray out and cause burns. Do not pour cold water onto the diesel engine cylinder block or cylinder head; this may cause the cylinder block of the diesel generator set to crack due to sudden cooling.
Emergency handling steps for coolant boil-over in diesel generator sets:
1. If a coolant boiling phenomenon occurs during diesel generator operation, first remove the load, the fuel injection quantity will automatically decrease, and the combustion temperature in the cylinder will drop rapidly. Reduce the engine speed to reduce heat generation by the engine.
2. After the generator speed is reduced, shut down slowly to avoid sudden shutdown causing thermal stress damage to components due to a sudden temperature drop. After shutdown, turn off the generator power and cut off the fuel supply to ensure safe shutdown.
3. After shutdown, wait for the generator to cool naturally. Generally, it is necessary to wait until the temperature drops below 60°C before carrying out subsequent handling.
The solutions to coolant boil-over in diesel generator sets mainly include checking the cooling system, cleaning the cooling system, checking the radiator, checking the water pump, and controlling the load. Find out the cause of the fault and take corresponding measures to solve the problem. For example, if the radiator or cooling system leaks, promptly check the cause of the leakage, eliminate the fault, and then add sufficient cooling water. Or adjust or replace the fan belt according to the situation, and inspect and repair the radiator, thermostat, etc.
The above are the common causes and solutions for the coolant boiling phenomenon of diesel generators. When encountering faults during the operation of diesel generating sets, do not panic, stay calm, find out where the fault is, and take appropriate solutions in a timely manner. If it feels difficult, it is recommended that professional technicians carry out the operation to ensure that the diesel generator set returns to normal operation as soon as possible.