How to Prevent 120kW Generator Set from Running at Small Load

Apr. 19, 2023

1. Preparation before startup. Before starting the engine, it is necessary to check whether the cooling water or antifreeze in the diesel engine water tank meets the requirements. If there is a shortage, it should be topped up. Pull out the oil dipstick to check if there is a shortage of lubricating oil. If there is a shortage, add it to the specified scale line, and carefully check the relevant components for any potential faults. If any faults are found, they should be promptly eliminated before starting the machine.


2. It is strictly prohibited to start the diesel engine with load. Before starting a diesel engine, it is important to note that the output air switch of 120kW generator must be in a closed state. After starting diesel engine of 120kW generator set, it needs to run at idle speed for 3-5 minutes (around 700rpm). In winter, the temperature is low, and the idle running time should be appropriately extended for a few minutes. After starting the diesel engine, the first thing to observe is whether the oil pressure is normal and whether there are any abnormal phenomena such as oil or water leaks (under normal circumstances, the oil pressure must be above 0.2MPa). If any abnormalities are found, immediately stop the machine for maintenance. If there are no abnormalities, increase the diesel engine speed to the rated speed of 1500 rpm. At this time, the 120kW generator displays a frequency of 50Hz and a voltage of 400V. Then, the output air switch can be closed and put into use. The 120kW generator set is not allowed to operate without load for a long time. (Long time no-load operation will cause the diesel fuel injected from the diesel engine nozzle to fail to burn completely, resulting in carbon deposition and air leakage of valves and piston ring.) If it is an automatic generator set, idle operation is not required, because the automatic generator set is generally equipped with a water heater to keep the diesel engine cylinder body at about 45Co, and the diesel engine can be powered on normally within 8-15 seconds after starting.


Shangchai genset


3. Pay attention to the working status during operation. During the operation of the generator set, a dedicated person should be on duty and frequently observe a series of possible faults, especially the changes in important factors such as oil pressure, water temperature, oil temperature, voltage, frequency, etc. In addition, it is also important to ensure that sufficient diesel fuel is available. If fuel is interrupted during operation, it may objectively cause on-load shutdown, which may lead to damage to the generator excitation control system and related components.


4. It is strictly prohibited to shut down under load. Before each shutdown, the load must be gradually cut off, and then the output air switch of the generator set must be turned off. The diesel engine must be slowed down to idle speed and run for about 3-5 minutes before stopping.


As for the hazards of small load operation of diesel generator set, we should all know that we must use the diesel generator set in strict accordance with the manufacturer's regulations and requirements, so as to extend its life. If you still have something unclear, you are welcome to consult Dingbo Power. Our company operates a variety of brands of diesel generator sets for you to choose, and there is always one suitable for you.

Follow Us

WeChat

WeChat

Contact Us

Mob.: +86 134 8102 4441

Tel.: +86 771 5805 269

Fax: +86 771 5805 259

E-mail: dingbo@dieselgeneratortech.com

Skype: +86 134 8102 4441

Add.: No.2, Gaohua Road, Zhengxin Science and Technology Park, Nanning, Guangxi, China.

Get in Touch

Enter your email and receive the latest news from us.

Copyright © Guangxi Dingbo Power Equipment Manufacturing Co., Ltd. All Rights Reserved | Sitemap Update cookies preferences | privacy-policy
Contact Us