Status Signal Category of the Automatic Control System of Diesel Generator Set

Sep. 26, 2021

The diesel generator set automation control system is composed of three parts: program control, simulation control and operation management control. The automatic diesel generator set control panel can automatically complete the control functions of the unit start and stop, power supply and power failure, and monitor the operating status of the unit. Measurement, display, over-limit alarm and protection, and the status signals of the automatic control system of diesel generator sets can be divided into the following four categories according to their functions:

 

(1) Start and stop signals. The start and stop signals of the automatic generator set mainly include the abnormal main power supply (including power loss, phase loss, voltage value exceeding the allowable value), and other signals that the user needs to start the generator set according to the specific purpose of the generator set.These signals are sent to the controller in a logical combination. When its logic value is "1", the generator set will start automatically and act according to the prescribed control flow; when its logic value is "0", the generator set will automatically stop after a delay.The detection of abnormal power supply signals usually uses phase-failure protectors, voltage comparators, etc. For some controllers with a power detection device, the detection of the power supply signal is carried out inside the controller, and no external detection device is required.

 

(2) Diesel engine working condition signal. In addition to the working conditions (such as automatic working conditions, manual working conditions), the diesel engine working conditions that need to be tested include whether the starting is successful, whether the diesel engine speed is normal, whether the pressure of the lubricating oil and the temperature of the diesel engine are abnormal, etc.

 

In order to protect the diesel engine, when the start fails, the diesel engine is overspeed, the lubricating oil pressure is too low or the temperature of the diesel engine is too high, the unit will automatically stop and give an alarm, and the system will automatically lock. Without manual intervention (unlocking), the unit will not start automatically even if the start signal is received.

 

Such signals are usually detected by dedicated sensors, such as rotational speed sensors, pressure sensors, and temperature sensors.


Status Signal Category of the Automatic Control System of Diesel Generator Set

 

(3) Generator status signal. In order to supply power to the load safely, it is necessary to detect the generator voltage, current, frequency and ATS status. When the above-mentioned power exceeds the limit, corresponding protection should be provided to avoid damage to the generator, cause an accident or reduce the quality of power supply.

 

(4) Other signals. In addition to the above signals, as an automatic control system, it also needs to detect battery voltage, charging voltage, fuel level, etc. to ensure that the generator set is always in a normal standby state and meets the requirements for starting at any time.In addition, the automated generator set monitoring system used for communication usually detects the signal of the room environment (temperature, humidity, door alarm, fire alarm, etc.).

 

The above is the status signal category of the diesel generator set automation control system that Dingbo Power has compiled and introduced for you. I believe you must have a better understanding of the composition of diesel generator sets. Dingbo Power is a company with 15 years of production experience. Diesel generator set manufacturer, the company has modern production base, professional technical research and development team, advanced manufacturing technology, perfect quality management system, sound after-sales service guarantee, can provide users with reliable diesel generator set solutions, welcome to contact by email dingbo@dieselgeneratortech.com.

 


Follow Us

WeChat

WeChat

Contact Us

Mob.: +86 134 8102 4441

Tel.: +86 771 5805 269

Fax: +86 771 5805 259

E-mail: dingbo@dieselgeneratortech.com

Skype: +86 134 8102 4441

Add.: No.2, Gaohua Road, Zhengxin Science and Technology Park, Nanning, Guangxi, China.

Get in Touch

Enter your email and receive the latest news from us.

Copyright © Guangxi Dingbo Power Equipment Manufacturing Co., Ltd. All Rights Reserved | Sitemap Update cookies preferences | privacy-policy
Contact Us