Operating Conditions Of 1000KVA Cummins Generator

Mar. 15, 2022

1. Continuous power (COP): Under agreed operating conditions, the generator set operates continuously with a constant load and an unlimited annual running time according to the high power maintained in accordance with the manufacturer's regulations.

2. Basic power (PRP): The high power and annual operating hours of the generator set for continuous operation under variable load are not limited under agreed operating conditions and are maintained according to the manufacturer's regulations. Average power output during 24 hours of operation shall not exceed 70% of PRP unless otherwise agreed with RIC engine manufacturer. In applications where the average power output Ppp is higher than the specified value, the continuous power factor should be used.

3. Limited operating Power (LTP): Under agreed operating conditions, the generator set can achieve 500 hours of high power per year as specified by the manufacturer. According to the calculation of 100% limited running power, the long running time is 500h per year.

4. Emergency backup power supply: The generator set shall be maintained under agreed operating conditions and manufacturer's regulations. Once the power supply is interrupted or under experimental conditions, the generator set is operating under strain load, with an annual operating time of up to 200 hours of ** power. Unless otherwise agreed with the manufacturer, the average power output allowed during 24 hours of operation shall not exceed 70% electrostatic precipitators.

At the same time, the standard also specifies the field conditions for the operation of the generator set: the field conditions are determined by the user, and the following rated field conditions are used when the field conditions are unknown and there are no other provisions.

1)Atmospheric pressure :89.9 kpa (or 1000 meters above sea level).

2) Ambient temperature :40℃.

3) Relative humidity :60%.


Operating Conditions Of 1000kva Cummins Generator


The rated output power on the nameplate of diesel generator set is generally divided into standard power, initial power and continuous power.

1) Standby power is defined as the maximum power that the generator set can run continuously for 300 hours between the specified maintenance cycle and the specified environmental conditions, and the maximum operating time per year is 500 hours. Equivalent to limited operating power (LTP) in national and ISO standards. Generally applicable to communications, buildings and other load changes of the accident emergency situation.

2) Common power refers to the maximum power existing in a variable power sequence with an unlimited number of possible operating hours per year between the specified maintenance cycle and the specified environmental conditions, which is equivalent to the basic power (PRP) in national and international organization for Standardization standards. Generally applicable to factories, mines, military and other frequent load changes.

3) Continuous power is defined as  power in a constant power sequence of unlimited possible operating time each year between the specified maintenance cycle and the specified environmental conditions. Equivalent to continuous power (COP) in national and ISO standards. In general, it is suitable for continuous operating conditions where the load varies **, such as being used as a power station or connected to a power supply.

 

For the application of diesel engine in data center, it is generally selected according to the common power when determining the unit power quota.

Due to the importance of data centers, electrical redundancy must be considered for power supply equipment under various operating conditions. The configuration of the generator set is no exception. The specific method is to configure the number of units according to the principle of N+1 or 2N when configuring the diesel engine system.

Guangxi Dingbo Power Equipment Manufacturing Co., Ltd. established in 2006, is an manufacturer of diesel generator in China, which integrates design, supply, commissioning and maintenance of diesel generator set. Product covers 1000kva cummins diesel generator, cummins 600kw diesel generator , 900kw generator containerized generator set, 1250kva perkins generator, 80kva perkins generator ,volvo diesel generator 650kva etc.

 


Follow Us

WeChat

WeChat

Contact Us

Mob.: +86 134 8102 4441

Tel.: +86 771 5805 269

Fax: +86 771 5805 259

E-mail: dingbo@dieselgeneratortech.com

Skype: +86 134 8102 4441

Add.: No.2, Gaohua Road, Zhengxin Science and Technology Park, Nanning, Guangxi, China.

Get in Touch

Enter your email and receive the latest news from us.

Copyright © Guangxi Dingbo Power Equipment Manufacturing Co., Ltd. All Rights Reserved | Sitemap Update cookies preferences | privacy-policy
Contact Us