Do You Know How the Diesel Generator Set Starts

Jul. 17, 2021

Diesel generator set is widely used in various fields closely related to us. Generally speaking, there are two ways to start diesel generator set, one is manual start and the other is automatic start. So do you know how these two startup modes are started respectively? The small edition of Dingbo Power will show you the correct starting steps of diesel generator set.

 

1、 Pre start check.

 

Before the inspection, for the diesel generator set with "automatic switching" function, in order to ensure safety, first place the generator start switch in the "manual" or "stop" position (or remove the connecting cable between the battery negative pole and the generator), and after the inspection, be sure to return it to the "automatic" position.

 

Check whether the oil level is within the scale, if not, add the same type of oil to the position within the scale, and check whether the fuel is enough.

 

Check whether the coolant is about 8cm below the water tank cover. If not, add soft water to the above position.

 

Check whether the electrolyte level is about 15mm on the electrode plate. If not, add distilled water to the above position.

 

Clean up the site of the generator set to ensure that the cooling ventilation channel is smooth.

 

Ensure that the main air switch of diesel generator set is in "off" state, and confirm whether the connection with "utility" has been disconnected.

 

Whether the belt is properly tightened.

 

2、 Manual start

 

After the diesel generator set is checked to be normal, press the manual mode, and then press the confirmation key to start the unit normally.

 

If the diesel generator set fails to start, restart after 30 seconds, and fails to start for three consecutive times, find out the cause and remove the fault before starting again.

 

After successful startup, check whether there is abnormal noise and vibration, whether there is oil leakage, water leakage and air leakage, and whether there is abnormal display on the control panel. Whether the oil pressure reaches the normal range (60 ~ 70psl) within 10 ~ 15 seconds after starting the diesel generator. If there is any abnormal phenomenon, it should be handled. After it is normal, turn on the main air switch of the diesel generator to start power supply.


Do You Know How the Diesel Generator Set Starts

 

3、 Manual shutdown.

 

Press the stop button on the control panel to stop the unit.

 

In case of emergency, press the emergency stop button immediately.

 

4、 Auto start.

 

Reset the buttons on the control panel.

 

Press the auto switch once and the unit will enter the standby mode.

 

Turn on the main air switch of diesel generator.

 

The diesel generator will start and deliver power in 5 ~ 8 seconds when the "mains" power is cut off.

 

If the diesel generator set cannot start automatically, press the red emergency stop button on the control panel to find out the cause and remove the fault before starting.

 

5、 Automatic shutdown.

 

When the "utility power" calls, the dual power conversion will automatically switch to "utility power", and the diesel generator will stop automatically after 3 minutes of no-load operation.

 

The above is the correct start-up steps of the diesel generator set arranged by generator manufacturer--- Guangxi Dingbo Power Equipment Manufacturing Co., Ltd. I hope it can help you. Dingbo power was founded in 2006. It is a professional diesel generator set manufacturer integrating the design, supply, commissioning and maintenance of diesel generator set. It can customize 30kw-3000kw various specifications of ordinary type, automatic type, automatic type 4. Diesel generator set with special power demand, such as protection, automatic switching and three remote monitoring, low noise and mobile, automatic grid connected system.If necessary, please contact us by emaildingbo@dieselgeneratortech.com.


Follow Us

WeChat

WeChat

Contact Us

Mob.: +86 134 8102 4441

Tel.: +86 771 5805 269

Fax: +86 771 5805 259

E-mail: dingbo@dieselgeneratortech.com

Skype: +86 134 8102 4441

Add.: No.2, Gaohua Road, Zhengxin Science and Technology Park, Nanning, Guangxi, China.

Get in Touch

Enter your email and receive the latest news from us.

Copyright © Guangxi Dingbo Power Equipment Manufacturing Co., Ltd. All Rights Reserved | Sitemap Update cookies preferences | privacy-policy
Contact Us