Requirements for Standby Diesel Generator Set for Fire Fighting

Jul. 15, 2022

Requirements for fire standby diesel generator set


(1) The standby generator set of class I high-rise buildings shall be equipped with automatic starting device and can supply power within 30 seconds.

(2) For standby generator sets in class II high-rise buildings, when it is difficult to use automatic starting, manual starting devices can be used.


When the regional power supply conditions cannot meet the power supply reliability requirements of fire-fighting primary load and secondary load, or it is not economical to obtain the second power supply from the regional substation, self-contained fire-fighting standby power supply (Dingbo diesel generator set) should be set.


Self provided fire standby power supply includes: emergency generator set, battery pack, uninterruptible power supply (UPS), fuel cell.

Requirements for Standby Diesel Generator Set for Fire Fighting

The requirements of self provided power supply for fire protection of high-rise buildings for self provided power generation equipment (self provided emergency generator set) are:


There are two kinds of self-contained emergency generator sets: diesel generator set and gas turbine generator set.


When selecting diesel generator set, high-speed diesel generator set and brushless automatic excitation device should be selected. Because the high-speed diesel generator set has the advantages of small size, light weight, reliable start-up and operation, etc. The brushless automatic excitation device has the characteristics of adapting to various starting modes, easy to realize unit automation or generator set, and when used together with the automatic voltage regulation device, the static voltage regulation rate can be guaranteed to be within ± 2.5%.


The self-contained emergency generator set shall be equipped with fast automatic starting and automatic power switching devices, and have the function of self starting for three consecutive times. For a class of high-rise buildings, the self starting switching time shall not exceed 30s; For other buildings, manual starting devices can also be used when it is difficult to use automatic starting. Generally, the unit should be started by electricity instead of compressed air. The total number of generator units should not exceed 2, and the unit capacity is generally 800KW and below.


Gas turbine generator device includes gas turbine, generator, control panel, starting battery, oil tank, air inlet and exhaust, silencer and other equipment. The units can be divided into fixed type, movable type and track type. The generator is a three-phase AC synchronous generator with brushless AC excitation.


The cooling of gas turbine does not need water cooling, but uses air to cool itself. In addition, combustion requires a lot of air, so the air demand of gas turbine unit is 2.5 ~ 4 times greater than that of diesel unit. Therefore, the installation location must consider the upper floor or roof with convenient air intake and exhaust, and should not be located in the basement, because the air intake and exhaust of the basement are difficult.

Follow Us

WeChat

WeChat

Contact Us

Mob.: +86 134 8102 4441

Tel.: +86 771 5805 269

Fax: +86 771 5805 259

E-mail: dingbo@dieselgeneratortech.com

Skype: +86 134 8102 4441

Add.: No.2, Gaohua Road, Zhengxin Science and Technology Park, Nanning, Guangxi, China.

Get in Touch

Enter your email and receive the latest news from us.

Copyright © Guangxi Dingbo Power Equipment Manufacturing Co., Ltd. All Rights Reserved | Sitemap Update cookies preferences | privacy-policy
Contact Us