Which Faults Cause Insufficient Power of 500KW Volvo Genset

Jul. 27, 2021

Do you know what faults cause insufficuent power of 500kw Volvo genset? 500KW generator manufacturer answers for you. 


1.The air filter is dirty.

The dirty air filter will increase the resistance and reduce the air flow, which will affect the proportion of air and diesel fuel, and the mixture will not burn completely, wasting diesel fuel, resulting in insufficient engine power. At this case, should clean the air filter core or remove the dust on the paper filter element as required, and replace the filter element if necessary.


2.Exhaust pipe blocked.

The blocked exhaust pipe will cause blocked exhaust, the suction link of the new working cycle will also be blocked, and the fuel efficiency will be reduced. The power of diesel generator decreases. Check whether the exhaust resistance increases due to too much carbon deposition in the exhaust pipe. Generally, the exhaust back pressure should not exceed 3.3kpa, and the carbon deposit in the exhaust pipe should be removed frequently at ordinary times.


500kw silent genset


3.The fuel supply advance angle is too large or too small.

Too large or too small fuel supply advance angle will cause the fuel injection time of the oil pump to be too early or too late, so that the combustion process is not in the best state. The fuel consumption of the diesel engine is increased, the exhaust temperature is increased, the noise is large, and the reliability of the diesel engine is reduced. At this time, check whether the fuel injection drive shaft adapter pin is loose. If it is loose, readjust the oil supply advance angle as required and tighten the screws.


4.Piston cylinder liner strained.

As the piston and cylinder liner are seriously strained or worn, and the friction loss increases due to the rubber binding of piston ring, the mechanical loss of the engine increases, the compression ratio decreases, the ignition is difficult or the combustion is insufficient, the lower inflation increases and the air leakage is serious. At this time, replace the cylinder liner, piston and piston ring.


5.There is a problem with the fuel system.

The air in the fuel filter or pipeline is blocked, resulting in blocked oil circuit and insufficient power. It is even difficult to catch fire. At this time, should clean the air entering the pipeline, clean the diesel filter element and replace it if necessary. The damage of fuel injection coupling causes oil leakage, seizure or poor atomization, which is easy to lead to cylinder shortage and insufficient engine power. It shall be cleaned, ground or renewed in time.


Insufficient fuel supply of the fuel injection pump will also cause insufficient power of Volvo genset. Should check, repair or replace the coupling parts in time and readjust the fuel supply of the fuel injection pump.


An important indicator to check whether Volvo diesel generator set works normally is whether the output power is stable and normal, and many users will be confused about why the power of the diesel generator set will be insufficient after running for a period of time. The insufficient power of the diesel generator set will affect the progress of various work. Dingbo power company, a diesel generator set manufacturer, said that if the diesel generator set is found to have insufficient power, the unit can be overhauled from the following seven aspects:


1.Check whether the diesel oil is mixed with rainwater or whether there is too much water. If the quality is qualified, other inspections shall be carried out.

2.Check the components of the fuel system for leakage. If there is no leakage, carry out other inspections.

3.Check whether the oil supply advance angle of the unit is compliant. If it is not compliant, it needs to be adjusted as required.

4.Remove the filter element of the diesel filter and the oil transfer pump, and check whether the oil inlet filter screen is clean. If the filter screen is clean, check whether the fuel injector is atomized well.

5.If the fuel injection pump does not operate well, contact the professional diesel generator set manufacturer to send special personnel to correct the fuel injection pump.

6.The valve clearance of the unit shall be adjusted in strict accordance with the requirements.

7.After the above six steps of maintenance, if the diesel generator unit still has insufficient power, check whether the cylinder pressure of the unit is normal.


Finally, Dingbo Power company want to tell you the methods to prevent the power decline of diesel generator set. If want the machine work well and normally, the most important thing is to maintain it well. Timely maintenance can not only improve the reliability of diesel generator set, but also prolong the service life of diesel generator set.


Dingbo Power company is as one of leading of diesel generator sets in China, can provide 58kw to 560kw Volvo genset. Of course, Dingbo Power also can provide other genset, Cummins, Pekins, Deutz, Yuchai, Shangchai, Ricardo, Weichai, MTU, Wuxi power etc. Welcome to contact us by email dingbo@dieselgeneratortech.com.

Follow Us

WeChat

WeChat

Contact Us

Mob.: +86 134 8102 4441

Tel.: +86 771 5805 269

Fax: +86 771 5805 259

E-mail: dingbo@dieselgeneratortech.com

Skype: +86 134 8102 4441

Add.: No.2, Gaohua Road, Zhengxin Science and Technology Park, Nanning, Guangxi, China.

Get in Touch

Enter your email and receive the latest news from us.

Copyright © Guangxi Dingbo Power Equipment Manufacturing Co., Ltd. All Rights Reserved | Sitemap Update cookies preferences | privacy-policy
Contact Us